44 DPA 250 S4 50-250 KW OPERATING MANUAL
5.3.1 Input dry ports (X3)
The UPS is equipped with digital input and output relays located in the UPS frame. The I/O are located
as follow:
• X1-X3 can hold Cable from 0.2mm2 – 1.5mm2
• All X3 (except X3 5/6 which is a 12VDC source) are inputs, cable max. R 50Ω at 20mA
Block Terminal Contact Signal On Display Function
GND
Battery Temperature
(Only the optional battery sen-
sor from ABB is compatible)
GND
GENERATOR_
OPER_ON
Generator Operation
(N.O.) Min. contact load 12V / 1mA
GND
PARRALEL_SW_OPEN
PARRALEL_SW_CLOSE
External Output Breaker
(N.O.)
Min. contact load 12V / 20mA.
GND
EXT_MAN_BYP
External Manual Bypass
(N.O.)
Min. contact load 20mA
(Max. 200mA)
GND
GND
REMOTE_
SHUTDOWN
RSD (Remote Shut down)
Default setting: disabled. Possibility to
enable and set NO or NC via NewSet.
-
REMOTE_
SHUTDOWN
RSD (Remote Shut down ) for external switch
Max. 250Vac/8A ;30Vdc/8A;
110Vdc/0.3A ;220Vdc/0.12A
-