12 MAINTENANCE BYPASS OPERATIONS
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
3. If present, turn to the ON position (close) the
maintenance bypass switch Q1 on all frames.
4. The message “MAN BYP CLOSED” will appear
in the event log of all modules.
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
5. If the maintenance bypass switch Q1 is not
installed in the frames, the load can be trans-
ferred directly to “External Maintenance By-
pass”.
In this case turn to the ON position (close)
the “External Maintenance Bypass” switch
and lock it to this position.
6. Load OFF all modules by means of the ON/
OFF buttons present on their control panels
(Always confirm with “ENTER” when re-
quired).
7. The output isolator Q2 installed on all frames
can be now opened (Turned to OFF position)
8. Turn to the OFF position (open) the battery
breakers present on all frames and external
battery cabinets or racks breakers or fuses
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Flashing red
The load is NOT protected by the DPA 250S4 UPS