Cycle time of PWM
in s [10...6,000]
For setting the cycle time for the pulse width modulation.
If the control value is received via a 1 bit value, this parameter serves as the basis for calculation of the
control of the output with
Bus voltage failure/recovery
Forced operation
Fault of the control value (control fault)
Characteristic correction
Opening time of valve drivein s [10...6,000]
With this parameter, a time is set in seconds that the connected valve requires to move from position 0%
(valve closed) to position 100% (valve fully open).
The time should be taken from the technical data of the valve, and it corresponds with the total runtime.
Closing time of valve drivein s [10...6,000]
With this parameter, a time is set in seconds that the connected valve requires to move from position
100% (valve open) to position 0% (valve fully closed).
The time should be taken from the technical data of the valve, and it corresponds with the total runtime.