ABB i-bus
®
KNX
Device technology
FCA/S 1.x.x.1 | 2CDC508134D0202 43
2.3.9 Output, lamp load 16 A
Lamps
Incandescent lamp load
2,500 W
Fluorescent lamps T5/T8
Uncompensated
Parallel compensated
DUO circuit
2,500 W
1,500 W
1,500 W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer
1,200 W
1,500 W
Halogen lamps 230 V
2,500 W
Dulux lamp
Uncompensated
Parallel compensated
1,100 W
1,100 W
Mercury-vapor lamp
Uncompensated
Parallel compensated
2,000 W
2,000 W
Switching capacity (switching contact)
Maximum peak inrush current I
p
(150 s)
400 A
Maximum peak inrush current I
p
(250 s)
320 A
Maximum peak inrush current I
p
(600 s)
200 A
Number of electronic ballasts (T5/T8, single
element)
1)
18 W (ABB EVG 1 x 18 SF)
23
24 W (ABB EVG-T5 1 x 24 CY)
23
36 W (ABB EVG 1 x 36 CF)
14
58 W (ABB EVG 1 x 58 CF)
11
80 W (Helvar EL 1 x 80 SC)
10
1)
For multiple element lamps or other types the number of electronic ballasts must be determined using the peak inrush current of the ballasts.