ABB i-bus
®
KNX
Commissioning
76 2CDC508134D0202 | FCA/S 1.x.x.1
3.2.3 Parameter window Outputs A...H
3.2.3.1 Parameter window Enable output A...D
In this parameter window, outputs A...D are enabled.
Fan coil operating mode
Options:
1 control value/1 valve
2 control values/1 valve
2 control values/1 valve/ with switching object
2 control values/2 valves
2 control values/2 valves/
with switching object
This parameter determines how the control value is processed.
Note
In the option 2 control values/2 valves (with or without switching object), one valve must be
parameterized as a heating valve and the other as a cooling valve, according to the installation
conditions.