EasyManuals Logo

ABB i-bus KNX User Manual

ABB i-bus KNX
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #182 background imageLoading...
Page #182 background image
ABB i-bus
®
KNX
Commissioning
180 2CDC508134D0202 | FCA/S 1.x.x.1
3.2.4.2.2 Parameter Distinction between long and short operation Yes
If the option Yes has been selected with the parameter Distinction between long and short operation, the
following parameters appear in Parameter window a: Switch sensor, p. 171:
Short operation -> Event 0
Long operation -> Event 1
<−−− NOTE
Input on operation
Options:
open
Closed
Open: The input is opened with actuation.
Closed: The input is closed with actuation.
If a normally open contact is connected to the input, the option Closed should be selected; on a
normally closed contact the option Open should be selected.
Long operation after …
Options:
0.6/0.8 s
1/1.2/1.5 s
2/3/4/5/6/7/8/9/10 s
Here the time period T
L
, after which an operation is considered a “long” operation, is defined.
Note
The remaining parameter descriptions can be found in Parameter Distinction between long
and short operation No, p. 173.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX and is the answer not in the manual?

ABB i-bus KNX Specifications

General IconGeneral
BrandABB
Modeli-bus KNX
CategoryController
LanguageEnglish

Related product manuals