KNX
Commissioning
128 2CDC508134D0202 | FCA/S 1.x.x.1
Limitation on forced operation
Options:
3, 2, 1, OFF
Unchanged
OFF
1
1, OFF
2
2, 1
2, 1, OFF
3
3, 2
3, 2, 1
This parameter sets which fan speed is set, or may not be over/undershot, when forced operation is
active.
3, 2, 1, OFF: All states are possible.
Unchanged: The state is retained.
OFF: Off
1: Limited to speed 1.*
1, OFF: limited to speed 1 and off.
2: Limited to speed 2.*
2, 1: limited to speeds 2 and 1.
2, 1, OFF: limited to speed 2, 1 and off.
3: Limited to speed 3.*
3, 2: limited to speeds 3 and 2.
3, 2, 1: limited to speeds 3, 2 and 1.
* The control value is ignored.
Enable automatic operation
Options:
No
Yes
Yes: Automatic operation is enabled. The Parameter window Automatic control (Multi-level), p. 137, also
appears.
Enable direct operation
Options:
No
Yes
Yes: Direct operation is enabled. The Parameter window Direct operation, p. 143, also appears.
Set startup/run-on
Options:
No
Yes
Yes: The function Set startup/run-on is enabled. The Parameter window Startup/Run-on, p. 145, also
appears.