ABB i-bus
®
KNX
Commissioning
140 2CDC508134D0202 | FCA/S 1.x.x.1
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only: The status is updated but not sent.
On change: The status is sent when a change occurs.
After request: The status is sent when a request occurs.
After a change or request: The status is sent on a change or a request.
Set control value during fault
Options:
No
Yes
This parameter sets the reaction in the event of an error.
Selection of option Yes:
Dependent parameter:
Control value in % [0...100]
Options:
0...30...100
This parameter sets what percentage to use for the control value in the event of an
error.
Reset time for automatic operation
in s [1...65,535], 0 = inactive
Options:
0
1…65,535
This parameter determines after which time the automatic operation is reset.
0: If 0 is selected, automatic operation is not reset.
1...65,535: If a time from a value of 1 is set, automatic operation is reset after the given time.
Note
A change of the parameter value will only become active after the next deactivation of automatic
operation by a direct communication object.