ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 147
Run-on behavior
Options:
No
Yes
This parameter activates a run-on for the fan. If the fan changes to a lower speed, it remains in the
previous speed for the parameterized run-on time and only then reduces the speed by one level.
If the fan goes through several speed changes, run-on times are executed successively, adding on those
times.
A run-on time of 0 seconds means that run-on is deactivated.
Run-on is executed regardless of where the speed change originates (automatic operation, direct
operation, manual procedure, fan switch off).
Selection of option Yes:
Dependent parameters:
Run-on times speed 3
in s [0...65,535]
Options:
0…20…65,535
Run-on times speed 2
in s [0...65,535]
Options:
0…20…65,535
Run-on times speed 1
in s [0...65,535]
Options:
0…20…65,535