Commissioning
186 2CDC508134D0202 | FCA/S 1.x.x.1
Scan input after download,
ETS reset and bus voltage recovery
Options:
No
Yes
No: The object value is not scanned after a download, ETS reset and bus voltage recovery.
Yes: The object value is scanned after a download, ETS reset and bus voltage recovery.
The following parameter appears:
Inactive wait state after bus voltage
recovery in s [0…65,535]
Options:
0…65,535
Here the waiting time after a bus voltage recovery is set. After the waiting time has elapsed the
state on the input terminals is scanned. The input reacts as if the state on the input terminals has
just changed.
Note
The inactive waiting time does not add to the actual, adjustable sending delay time. This can be
set separately.