EasyManua.ls Logo

ABB i-bus KNX - Page 72

ABB i-bus KNX
264 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB i-bus
®
KNX
Commissioning
70 2CDC508134D0202 | FCA/S 1.x.x.1
Rate of telegrams
Options:
Do not limit
1/2/3/5/10/20 telegram(s)/second
0.05/0.1/0.2/0.3/0.5 seconds/telegram
Using this parameter, the bus load generated by the device can be limited.
1/2/3/5/10/20 telegram(s)/second: X telegrams per second are sent.
0.05/0.1/0.2/0.3/0.5 seconds/telegram: A telegram is sent every x seconds.
Enable communication object
"In operation", 1 bit
Options:
No
Send value 0 cyclically
Send value 1 cyclically
The communication object In operation indicates that the device on the bus is working properly. This cyclic
telegram can be monitored by an external device.
Send value 0/value 1 cyclically: The value 0 or 1 is sent cyclically and the 1-bit communication object
In operation is enabled.
Dependent parameter:
Telegram is repeated
Options:
Every second
Every 2/3/5/10/30/60 seconds
Every 2/3/5/10/30/60 minutes
Every 2/3/5/10/12 hours
Note
After bus voltage recovery, the communication object sends its value after the set sending and
switching delay.

Table of Contents

Related product manuals