DEFAULT DATA MAP DATA MAPPING
46 1TGC908004M0201
Modbus
Function
Code
Modbus
Register
Device
Number
Description Remarks
2
11001 1 Stopped 1 = Motor Stopped or
Tripped or Feeder
open
2
11002 1 Runs 1 = Motor Runs or
Feeder closed
2
11003 1 CW or K1 1 = Motor Runs Clock-
wise
2
11004 1 CCW or K2 1 = Motor Runs Coun-
ter Clockwise
2
11005 1 Ready 1 = Off and Ready for
Operation. No
alarm/trip is available
2 11006 1 Alarm 1 = Any Alarm condi-
tion of protection or
supervision functions.
2 11007 1 New Trip 1 = Any Trip condition
of the protection or
supervision functions
2 11008 1 Test 1 = Main switch set to
test position. (Motor
cannot start)
2 11009 1 HW local 1 = Control Access is
selected to hardwired
I/O from Local / Re-
mote input on M
10
x
-
M
2 11010 1 Bus local 1 = Control Access is
passed to any control
station on the switch-
gear control network.
2 11011 1 Remote 1=Control Access is
passed to the Process
Control System
2 11012 1 DI0 1= Digital Input 0 of
M
10
x
-
M is on
Continued on the next page