DATA MAPPING DEFAULT DATA MAP
1TGC908004M0201 47
Modbus
Function
Code
Modbus
Register
Device
Number
Description Remarks
2 11013 1 DI1 1= Digital Input 1 of
M10x-M is on
2 11014 1 DI2 1= Digital Input 2 of
M
10
x
-
M is on
2 11015 1 DI3 1= Digital Input 3 of
M
10
x
-
M is on
2 11016 1 DI4 1= Digital Input 4 of
M10x-M is on
2 11017 1 DI8 1= Digital Input 8 of
M
10
x
-
M is on
2 11018 1 DI9 1= Digital Input 9 of
M
10
x
-
M is on
2 11019 1 DI10 1= Digital Input 10 of
M10x-M is on
2 11020 1 DI11 1= Digital Input 11 of
M
10
x
-
M is on
2 11021 1 DI12 1= Digital Input 12 of
M
10
x
-
M is on
2
11022 2 Stopped 1 = Motor Stopped or
Tripped or Feeder
open
2
11023 2 Runs 1 = Motor Runs or
Feeder closed
2
11024 2 CW or K1 1 = Motor Runs Clock-
wise
:
:
:
:
:
2
13668 128 Stopped 1 = Motor Stopped or
Tripped or Feeder
open
2
13669 128 Runs 1 = Motor Runs or
Feeder closed
2
13670 128 CW or K1 1 = Motor Runs Clock-
wise