DEFAULT DATA MAP DATA MAPPING
48 1TGC908004M0201
Modbus
Function
Code
Modbus
Register
Device
Number
Description Remarks
2
13671 128 CCW or K2 1 = Motor Runs Coun-
ter Clockwise
2
13672 128 Ready 1 = Off and Ready for
Operation. No
alarm/trip is available
2 13673 128 Alarm 1 = Any Alarm condi-
tion of protection or
supervision functions.
2 13674 128 New Trip 1 = Any Trip condition
of the protection or
supervision functions
2 13675 128 Test 1 = Main switch set to
test position. (Motor
cannot start)
2 13676 128 HW local 1 = Control Access is
selected to hardwired
I/O from Local / Re-
mote input on M
10
x
-
M
2 13677 128 Bus local 1 = Control Access is
passed to any control
station on the switch-
gear control network.
2 13678 128 Remote 1=Control Access is
passed to the Process
Control System
2 13679 128 DI0 1= Digital Input 0 of
M
10
x
-
M is on
2 13680 128 DI1 1= Digital Input 1 of
M
10
x
-
M is on
2 13681 128 DI2 1= Digital Input 2 of
M
10
x
-
M is on
2 13682 128 DI3 1= Digital Input 3 of
M
10
x
-
M is on
2 13683 128 DI4 1= Digital Input 4 of
M
10
x
-
M is on
Continued on the next page