Planning the electrical installation 41
Typical installation example
Mount AC filter and
MicroFlex e150 on the
same metal panel.
AC power
from fuses
or reactor
AC power wires should be as short as
possible, typically less than 0.3 m (1 ft).
Longer wires must be shielded as shown.
Wire colors can vary according to region.
Connect AC power
cable shield to metal
panel, using
conductive shield
earth/ground clamps.
On painted panels,
remove paint to
expose bare metal.
Drive earth wire
must be at least
10 mm
2
(7 AWG)
Protective Earth
(PE)
DO NOT TOUCH!
Brake resistors can
become extremely hot!
Locate away from
vulnerable components
and wiring.
CAUTION
Installation cabinet ‘star point’