logical commands (for selector switches or voltage controllers) by inputting an
integer number. ITBGAPC function has a logical node mapping in IEC 61850.
The Integer to Boolean 16 conversion with logic node representation function
(ITBGAPC) will transfer an integer with a value between 0 to 65535
communicated via IEC 61850 and connected to the ITBGAPC function block to a
combination of activated outputs OUTx where 1≤x≤16.
The values of the different OUTx are according to the Table 
26.
If the BLOCK input is activated, it freezes the logical outputs at the last value.
Table 26: Output signals
Name of OUTx Type Description Value when
activated
Value when
deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0
The sum of the numbers in column “Value when activated” when all OUTx
(1≤x≤16) are active equals 65535. This is the highest integer that can be converted
by the ITBGAPC function block.
14.12  Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
14.12.1  Identification
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Elapsed time integrator TEIGAPC - -
1MRK 505 393-UEN B Section 14
Logic
Line differential protection RED650 2.2 IEC 311