EasyManuals Logo

ABB RED650 Applications Manual

ABB RED650
454 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #156 background imageLoading...
Page #156 background image
The minimum primary setting (Is) for the instantaneous phase overcurrent
protection is then:
min
1.3
s
I I³ ×
EQUATION79 V3 EN-US (Equation 96)
The protection function can be used for the specific application only if this setting
value is equal to or less than the maximum fault current that the IED has to clear, I
F
in Figure 71.
IEC09000024-1-en.vsd
~ ~
Z
A
Z
B
Z
L
A B
IED
I
F
Fault
IEC09000024 V1 EN-US
Figure 71: Fault current: I
F
100
Is
IP
IBase
>>= ×
EQUATION1147 V3 EN-US
(Equation 97)
8.1.3.2 Meshed network with parallel line
M12915-34 v7
In case of parallel lines, the influence of the induced current from the parallel line
to the protected line has to be considered. One example is given in Figure 72,
where the two lines are connected to the same busbars. In this case the influence of
the induced fault current from the faulty line (line 1) to the healthy line (line 2) is
considered together with the two through fault currents I
fA
and I
fB
mentioned
previously. The maximal influence from the parallel line for the IED in Figure 72
will be with a fault at the C point with the C breaker open.
A fault in C has to be applied, and then the maximum current seen from the IED
(I
M
) on the healthy line (this applies for single-phase-to-earth and two-phase-to-
earth faults) is calculated.
Section 8 1MRK 505 393-UEN B
Current protection
150 Line differential protection RED650 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB RED650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RED650 and is the answer not in the manual?

ABB RED650 Specifications

General IconGeneral
BrandABB
ModelRED650
CategoryProtection Device
LanguageEnglish

Related product manuals