input signal to the function. The function generates alarms based on the received
information.
15.2.3 Setting guidelines
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v3
The parameters for Gas medium supervision SSIMG can be set via local HMI or
Protection and Control Manager PCM600.
Operation: This is used to disable/enable the operation of gas medium supervision
i.e. Off/On.
PresAlmLimit: This is used to set the limit for a pressure alarm condition in the
circuit breaker.
PresLOLimit: This is used to set the limit for a pressure lockout condition in the
circuit breaker.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in
the circuit breaker.
TempLOLimit: This is used to set the limit for a temperature lockout condition in
the circuit breaker.
tPressureAlarm: This is used to set the time delay for a pressure alarm indication,
given in s.
tPressureLO: This is used to set the time delay for a pressure lockout indication,
given in s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication,
given in s.
tTempLockOut: This is used to set the time delay for a temperature lockout
indication, given in s.
tResetPressAlm: This is used for the pressure alarm indication to reset after a set
time delay in s.
tResetPressLO: This is used for the pressure lockout indication to reset after a set
time delay in s.
tResetTempLO: This is used for the temperature lockout indication to reset after a
set time delay in s.
tResetTempAlm: This is used for the temperature alarm indication to reset after a set
time delay in s.
Section 15 1MRK 505 393-UEN B
Monitoring
328 Line differential protection RED650 2.2 IEC
Application manual