where:
t
op
is operate time
k is time multiplier of the inverse time curve
a, b, c, p are settings that will model the inverse time characteristic
6.1.3.6 Settings examples
M12541-349 v3
M12941-3 v8
Setting example with a power transformer in the protected zone
Figure 44 shows a line with a power transformer in the protected zone. Circuit
impedances are presented in Figure 45. The protected zone is limited by three
current transformers: CT1, CT2 and CT3. IEDs are situated in two separate
substations 1 and 2.
The circuit is protected by two terminals 1 and 2. These terminals process the same
data except for minor distortion in data that takes place during communication
between them. Both terminals operate as masters. If at least one of them indicates
an internal fault, the protected circuit is disconnected.
IED 2
Line 50 km
CT 3
Substation 2
Substation 1
Current samples from terminals 2 and 3
Current samples from terminal 1
CT 2
Yd1
200 MVA,
220 / 70 kV,
525 / 1650 A
Y
d
220 kV, 600 A
CB 1
terminal
2 terminal
3
CB 2
CB 3
terminal
1
CT 1
IED 1
IEC05000534-2-en.vsdx
IEC05000534 V2 EN-US
Figure 44: Line differential protection with a power transformer in the
protected zone
1MRK 505 393-UEN B Section 6
Differential protection
Line differential protection RED650 2.2 IEC 97
Application manual

Table of Contents

Other manuals for ABB RED650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RED650 and is the answer not in the manual?

ABB RED650 Specifications

General IconGeneral
BrandABB
ModelRED650
CategoryProtection Device
LanguageEnglish

Related product manuals