ABB REF615 G - Three-phase directional overcurrent protection DPHxPDOC

ABB REF615 G
896 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MF
MF
OUTGOING
INCOMING
PH3LPTOC
PH3HPTOC
PH3IPTOC
CCBRBRF
INRPHAR
PH3LPTOC
PH3HPTOC
PH3IPTOC
CCBRBRF
MF
OUTGOING
INRPHAR
Line type 2
Line type 1
I
k
max
I
k
min
I
k
max
I
k
min
I
k
max
I
k
min
9
8
7
GUID-0A032F35-2E27-4AAE-B698-D33E1893B3EA V1 EN
Figure 82: Functionality of numerical multiple-stage overcurrent protection
The coordination plan is an effective tool to study the operation of time-selective
operation characteristics. All the points mentioned earlier, required to define the
overcurrent protection parameters, can be expressed simultaneously in a
coordination plan. In Figure 75, the coordination plan shows an example of
operation characteristics in the LV-side incoming feeder and radial outgoing feeder.
Section 4 1YHT530004D05 D
Protection functions
170 615 series
Technical Manual