Name Type Values (Range) Unit Description
ANGL_UA_IA FLOAT32 -180...180 deg Measured angle value
between phase A
voltage and current
TIMER_STS Enum 0=Timer off
1=Lower timer1
on
2=Raise timer1
on
3=Lower timer2
on
4=Raise timer2
on
5=Fast lower T
on
  Timer T1, T2 or fast
lower timer active
OPR_MODE_STS Enum 0=Not in use
1=Manual
2=Auto single
3=Auto master
4=Auto follower
5=MCC
6=NRP
  The acting operation
mode of the function
block
U_CTL FLOAT32 0.000...3.000 xUn Control voltage, Up,
target voltage level
UD_CTL FLOAT32 -2.000...2.000 xUn Voltage difference
between Measured
voltage - Control
Voltage: Um - Up
I_CIR FLOAT32 -10.00...10.00 xIn Calculated circulating
current - calculated in
operation modes NRP
and MCC
LDC FLOAT32 -2.00...2.00 xUn Calculated line drop
compensation
BLK_STATUS INT32 0...127   Bit-coded output
showing the blocking
status for the next
operation
ALARM_REAS Enum 0=No alarm
1=Cmd error
2=TCO error
3=Cmd + TCO
err
4=Pump error
5=Pump + cmd
err
6=Pump + TCO
err
7=Pmp+TCO
+cmd err
  Status and reason for
alarm
OP_TM_NUM_H INT32 0...2147483647   Number of controls for
own tap changer during
last hour
Table continues on next page
1YHT530004D05 D Section 9
Control functions
615 series 761
Technical Manual