To enable active setting group changing via binary input, connect any of the (free)
binary inputs to SGCB-block input named ActSG using PCM600 and set the setting
SG follow input to “TRUE”.
Table 56: Active setting group binary input state
BI state Active setting group
OFF 1
ON 2
The setting group parameter is overridden when a binary input is used for changing
the active setting group.
Table 57: Settings
Parameter Setting Value Default Description Access rights
Setting group Active group 1...4 1 Selected
active group
RWRW
Not all parameters belong to a setting group. For example protection function enable/
disable settings are not part of a setting group.
1MRS756378 D Section 4
Basic functions
REF615 131
Application Manual