Section 8 Impedance protection
8.1 Distance measuring zone, quadrilateral
characteristic for series compensated lines
ZMCPDIS, ZMCAPDIS, ZDSRDIR
SEMOD168167-1 v3
8.1.1 Identification
SEMOD168165-2 v2
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Distance measuring zone, quadrilateral
characteristic for series compensated
lines (zone 1)
ZMCPDIS
S00346 V1 EN-US
21
Distance measuring zone, quadrilateral
characteristic for series compensated
lines (zone 2-5)
ZMCAPDIS
S00346 V1 EN-US
21
Directional impedance quadrilateral,
including series compensation
ZDSRDIR
IEC09000167 V1 EN-US
21D
8.1.2 Application
SEMOD168236-1 v1
8.1.2.1 Introduction
SEMOD168232-4 v2
Sub transmission networks are being extended and often become more and more
complex, consisting of a high number of multi-circuit and/or multi terminal lines of
very different lengths. These changes in the network will normally impose more
stringent demands on the fault clearing equipment in order to maintain an
unchanged or increased security level of the power system.
The distance protection function is designed to meet basic requirements for
application on transmission and sub transmission lines (solid earthed systems)
although it also can be used on distribution levels.
1MRK 506 369-UEN B Section 8
Impedance protection