EasyManua.ls Logo

ABB REL670 2.2 IEC - System Earthing

ABB REL670 2.2 IEC
908 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.4.2.2 System earthing
SEMOD154453-11 v3
The type of system earthing plays an important role when designing the protection
system. In the following some hints with respect to distance protection are
highlighted.
Solid earthed networks
SEMOD154453-14 v5
In solid earthed systems the transformer neutrals are connected solidly to earth
without any impedance between the transformer neutral and earth.
IEC05000215 V2 EN-US
Figure 121: Solidly earthed network
The earth-fault current is as high as or even higher than the short-circuit current.
The series impedances determine the magnitude of the earth-fault current. The
shunt admittance has very limited influence on the earth-fault current. The shunt
admittance may, however, have some marginal influence on the earth-fault current
in networks with long transmission lines.
The earth-fault current at single phase-to-earth in phase L1 can be calculated as
equation
148:
L1 L1
0
1 2 0 f 1 N f
3 U U
3I
Z Z Z 3Z Z ZZ
×
= =
+ + + + +
EQUATION1267 V3 EN-US (Equation 148)
Where:
U
L1
is the phase to earth voltage (kV) in the faulty phase before fault
Z
1
is the positive sequence impedance (Ω/phase)
Z
2
is the negative sequence impedance (Ω/phase)
Z
0
is the zero sequence impedance (Ω/phase)
Z
f
is the fault impedance (Ω), often resistive
Z
N
is the earth return impedance defined as (Z
0
-Z
1
)/3
The voltage on the healthy phases is generally lower than 140% of the nominal
phase-to-earth voltage. This corresponds to about 80% of the nominal phase-to-
phase voltage.
Section 8 1MRK 506 369-UEN B
Impedance protection
236 Line distance protection REL670 2.2 IEC
Application manual

Table of Contents

Related product manuals