2.5 Communication
GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v16
IEC 61850 or function
name
ANSI Function description Line Distance
REL670
(Customized)
REL670 (A41)
REL670 (A42)
REL670 (B42)
REL670 (D42)
Station communication
ADE LON communication protocol 1 1 1 1 1
HORZCOMM Network variables via LON 1 1 1 1 1
IEC 61850-8-1 IEC 61850 1 1 1 1 1
GOOSEINTLKRCV Horizontal communication via
GOOSE for interlocking
59 59 59 59 59
GOOSEBINRCV GOOSE binary receive 16 16 16 16 16
GOOSEDPRCV GOOSE function block to receive
a double point value
64 64 64 64 64
GOOSEINTRCV GOOSE function block to receive
an integer value
32 32 32 32 32
GOOSEMVRCV GOOSE function block to receive
a measurand value
60 60 60 60 60
GOOSESPRCV GOOSE function block to receive
a single point value
64 64 64 64 64
MULTICMDRCV,
MULTICMDSND
Multiple command and transmit 60/10 60/10 60/10 60/10 60/10
AGSAL Generic security application
component
1 1 1 1 1
LD0LLN0 IEC 61850 LD0 LLN0 1 1 1 1 1
SYSLLN0 IEC 61850 SYS LLN0 1 1 1 1 1
LPHD Physical device information 1 1 1 1 1
PCMACCS IED configuration protocol 1 1 1 1 1
FSTACCS Field service tool access 1 1 1 1 1
IEC 61850-9-2 Process bus
communication, 8 merging units
0-1 1-P30 1-P30 1-P30 1-P30
ACTIVLOG Activity logging 1 1 1 1 1
ALTRK Service tracking 1 1 1 1 1
PRP IEC 62439-3 Parallel redundancy
protocol
0-1 1-P23 1-P23 1-P23 1-P23
HSR IEC 62439-3 High-availability
seamless redundancy
0-1 1-P24 1-P24 1-P24 1-P24
Table continues on next page
1MRK 506 369-UEN B Section 2
Application
Line distance protection REL670 2.2 IEC 55
Application manual