ABB REL670 2.2 IEC
908 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
0
0 1
2 1 0
m
f
Z
K
Z Z R
= -
× + +
EQUATION1426 V1 EN-US (Equation 131)
If the denominator in equation 131 is called B and Z0m is simplified to X0m, then
the real and imaginary part of the reach reduction factor for the overreaching zones
can be written as:
( )
( )
( ) ( )
2 2
0 Re
Re 0 1
Re Im
X m B
K
B B
×
= -
+
EQUATION1427 V2 EN-US (Equation 132)
( )
( )
( ) ( )
2 2
0 Im
Im 0
Re Im
X m B
K
B B
×
=
+
EQUATION1428 V2 EN-US (Equation 133)
Parallel line is out of service and earthed in both ends
SEMOD55087-77 v3
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit
for the single phase-to-earth faults.
Set the values of the corresponding zone (zero-sequence resistance and reactance)
equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
+
è ø
ç ÷
æ ö
×=
EQUATION561 V1 EN-US (Equation 134)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
è ø
ç ÷
æ ö
×=
EQUATION562 V1 EN-US (Equation 135)
8.3.3.6 Setting of reach in resistive direction
SEMOD55087-84 v7
Set the resistive reach R1 independently for each zone.
Set separately the expected fault resistance for phase-to-phase faults RFPP and for
the phase-to-earth faults RFPE for each zone. For each distance zone, set all
remaining reach setting parameters independently of each other.
The final reach in resistive direction for phase-to-earth fault loop measurement
automatically follows the values of the line-positive and zero-sequence resistance,
and at the end of the protected zone is equal to equation
136.
1MRK 506 369-UEN B Section 8
Impedance protection
Line distance protection REL670 2.2 IEC 229
Application manual