Figure 408: Example of a station configuration with the IED receiving analogue
values from merging units
21.3.2 Setting guidelines
GUID-29B296B3-6185-459F-B06F-8E7F0C6C9460 v4
Merging Units (MUs) have several settings on local HMI under:
Section 21 1MRK 506 369-UEN B
Station communication
816 Line distance protection REL670 2.2 IEC
Application manual