EasyManua.ls Logo

ABB REL670 2.2 IEC - Zone Reach Setting Higher than Minimum Load Impedance

ABB REL670 2.2 IEC
908 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
load
1.6 ZRFPPZx
EQUATION579 V3 EN-US (Equation 397)
Equation 397 is applicable only when the loop characteristic angle for the phase-to-
phase faults is more than three times as large as the maximum expected load-
impedance angle. More accurate calculations are necessary according to
equation 398.
load min
R1Zx
RFPPZx 1.6 Z cos sin
X1Zx

IECEQUATION2307 V2 EN-US (Equation 398)
All this is applicable for all measuring zones when no Power swing detection
function ZMRPSB is activated in the IED. Use an additional safety margin of
approximately 20% in cases when a ZMRPSB function is activated in the IED,
refer to the description of Power swing detection function ZMRPSB.
8.13.4.9 Zone reach setting higher than minimum load impedance
GUID-78D0227F-2568-4C9A-8921-45812B4ABAF2 v5
The impedance zones are enabled as soon as the (symmetrical) load impedance
crosses the vertical boundaries defined by RLdFw and RLdRv
[9]
or the lines
defined by ArgLd. So, it is necessary to consider some margin. It is recommended
to set RLdFw and RLdRv to 90% of the per-phase resistance that corresponds to
maximum load.
min
0.9
load
RLdFw R< ×
IECEQUATION2419 V2 EN-US (Equation 399)
min
0.9
load
RLdRv R< ×
IECEQUATION2420 V2 EN-US (Equation 400)
The absolute value of the margin to the closest ArgLd line should be of the same
order, that is, at least 0.1 • Z
load min
.
The load encroachment settings are related to a per-phase load impedance in a
symmetrical star-coupled representation. For symmetrical load or three-phase and
phase-to-phase faults, this corresponds to the per-phase, or positive-sequence,
impedance. For a phase-to-earth fault, it corresponds to the per-loop impedance,
including the earth return impedance.
[9] RLdRv=RLdRvFactor*RLdFw
1MRK 506 369-UEN B Section 8
Impedance protection
Line distance protection REL670 2.2 IEC 403
Application manual

Table of Contents

Related product manuals