EasyManua.ls Logo

ABB REL670 2.2 IEC - Page 408

ABB REL670 2.2 IEC
908 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Z
loadmin
U
2
S
-------=
EQUATION571 V1 EN-US (Equation 393)
Where:
U is the minimum phase-to-phase voltage in kV
S is the maximum apparent power in MVA.
The load impedance [Ω/phase] is a function of the minimum operation voltage and
the maximum load current:
Z
load
U
min
3 I
max
×
----------------------
=
EQUATION574 V1 EN-US (Equation 394)
Minimum voltage U
min
and maximum current I
max
are related to the same
operating conditions. Minimum load impedance occurs normally under emergency
conditions.
To avoid load encroachment for the phase-to-earth measuring elements, the set
resistive reach of any distance protection zone must be less than 80% of the
minimum load impedance.
0.8
load
RFPEZx Z
EQUATION792 V2 EN-US (Equation 395)
This equation is applicable only when the loop characteristic angle for the single
phase-to-earth faults is more than three times as large as the maximum expected
load-impedance angle. For the case when the loop characteristic angle is less than
three times the load-impedance angle, more accurate calculations are necessary
according to equation
396.
min
21 0
0.8 cos sin
21 0
load
RZx R Zx
RFPEZx Z
XZx X Zx



EQUATION578 V5 EN-US
(Equation 396)
Where:
ϑ is a maximum load-impedance angle, related to the maximum load power.
To avoid load encroachment for the phase-to-phase measuring elements, the set
resistive reach of any distance protection zone must be less than 160% of the
minimum load impedance.
Section 8 1MRK 506 369-UEN B
Impedance protection
402 Line distance protection REL670 2.2 IEC
Application manual

Table of Contents

Related product manuals