8.14.3 Setting guidelines
SEMOD52042-5 v5
Setting guidelines are prepared in the form of a setting example for the protected
power line as part of a two-machine system presented in figure
224.
99001019.vsd
~~
E
A
d
A
= const
d
B
= f(t)
E
B
A B
Z
SA
Z
SB
Z
L
R
IEC99001019 V1 EN-US
Figure 224: Protected power line as part of a two-machine system
Reduce the power system with protected power line into an equivalent two-
machine system with positive sequence source impedances Z
SA
behind the
protective relay R and Z
SB
behind the remote end bus B. Observe the fact that these
impedances cannot be directly calculated from the maximum three-phase short
circuit currents for faults on the corresponding busbar. It is necessary to consider
separate contributions of different connected circuits.
The required data is as follows:
400
r
U kV=
EQUATION1321 V1 EN-US
Rated system voltage
min
380U kV=
EQUATION1322 V1 EN-US
Minimum expected system voltage under critical system
conditions
50
r
f Hz=
EQUATION1323 V1 EN-US
Rated system frequency
400
3
p
U kV=
EQUATION1324 V1 EN-US
Rated primary voltage of voltage (or potential) transformers
used
0.11
3
s
U kV=
EQUATION1325 V1 EN-US
Rated secondary voltage of voltage (or potential) transformers
used
1200
p
I A=
EQUATION1326 V1 EN-US
Rated primary current of current transformers used
1
s
I A=
EQUATION1327 V1 EN-US
Rated secondary current of current transformers used
Table continues on next page
1MRK 506 369-UEN B Section 8
Impedance protection
Line distance protection REL670 2.2 IEC 409
Application manual