With correct setting of the primary CT direction, CTStarPoint set to FromObject or
ToObject, a positive quantities always flowing towards the protected object and a
direction defined as Forward always is looking towards the protected object. The
following examples show the principle.
4.2.2.1 Example 1
SEMOD55055-23 v6
Two IEDs used for protection of two objects.
IEC05000753 V2 EN-US
Figure 7: Example how to set CTStarPoint parameters in the IED
Figure 7 shows the normal case where the objects have their own CTs. The settings
for CT direction shall be done according to the figure. To protect the line, direction
of the directional functions of the line protection shall be set to Forward. This
means that the protection is looking towards the line.