EasyManua.ls Logo

ABB REL670 2.2 IEC - Tapped Line Application

ABB REL670 2.2 IEC
908 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
( )
( )
( )
2
1 0
0
1 0
0
1 0
1
2
3
1
1
2 3
2
3
E f
m
U
f
f
Z Z R
Z
K
Z Z Z R
Z Z R
× × + +
= = -
× × + +
× × + +
EQUATION1284 V1 EN-US (Equation 350)
This means that the reach is reduced in reactive and resistive directions. If the real
and imaginary components of the constant A are equal to equation 351 and
equation
352.
Re( ) 0 (2 1 0 3 ) 0 ( 0 2 1)A R R R Rf X X X= × × + + × - × + ×
EQUATION1285 V1 EN-US (Equation 351)
0 1 0 1 0 1 0
Im( ) (2 3 ) (2 )A X R R R R X X= × × + + × + × × +
EQUATION1286 V1 EN-US (Equation 352)
The real component of the KU factor is equal to equation 353.
Re
Re
Re Im
K
A X
A A
u
m
( )
= +
( )
( )
+
( )
1
0
2
2 2
EQUATION1287 V3 EN-US (Equation 353)
The imaginary component of the same factor is equal to equation 354.
( )
( )
( ) ( )
2
0
2 2
Im
Im
Re Im
m
U
A X
K
A A
×
=
+
é ù é ù
ë û ë û
EQUATION1288 V2 EN-US (Equation 354)
Ensure that the underreaching zones from both line ends will overlap a sufficient
amount (at least 10%) in the middle of the protected circuit.
8.13.2.7 Tapped line application
GUID-4DFD6015-E97C-4F7E-84CA-C7CD2438C55A v1
1MRK 506 369-UEN B Section 8
Impedance protection
Line distance protection REL670 2.2 IEC 371
Application manual

Table of Contents

Related product manuals