15.7.2 Application
SEMOD55391-5 v8
Generic communication function for Double Point indication (DPGAPC) function
block is used to send double point position indication to other systems, equipment
or functions in the substation through IEC 61850-8-1 or other communication
protocols. It is especially intended to be used in the interlocking station-wide
logics. To be able to get the signals into other systems, equipment or functions, one
must use other tools, described in the Engineering manual, and define which
function block in which systems, equipment or functions should receive this
information.
More specifically, DPGAPC function reports a combined double point position
indication output POSITION, by evaluating the value and the timestamp attributes
of the inputs OPEN and CLOSE, together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputs
determine the two-bit integer value of the output POSITION. The timestamp of the
output POSITION will have the latest updated timestamp of the inputs OPEN and
CLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position to
intermediated state.
When the value of the input signal VALID changes, the timestamp of the output
POSITION will be updated as the time when DPGAPC function detects the
change.
Refer to Table
52 for the description of the input-output relationship in terms of the
value and the quality attributes.
Table 52: Description of the input-output relationship
VALID
OPEN CLOSE
POSITION
Value Description
0 - - 0 Intermediate
1 0 0 0 Intermediate
1 1 0 1 Open
1 0 1 2 Closed
1 1 1 3 Bad State
15.7.3 Setting guidelines
SEMOD55398-5 v5
The function does not have any parameters available in the local HMI or PCM600.