EasyManua.ls Logo

ABB REL670 2.2 IEC - Interlocking for Bus-Section Disconnector A1 A2_DC

ABB REL670 2.2 IEC
908 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15.4.6 Interlocking for bus-section disconnector A1A2_DC
IP14159-1 v2
15.4.6.1 Application
M13544-3 v7
The interlocking for bus-section disconnector (A1A2_DC) function is used for one
bus-section disconnector between section 1 and 2 according to figure
338.
A1A2_DC function can be used for different busbars, which includes a bus-section
disconnector.
WA1 (A1) WA2 (A2)
QB
QC1 QC2
A1A2_DC
en04000492.vsd
IEC04000492 V1 EN-US
Figure 338: Switchyard layout A1A2_DC
M13542-4 v4
The signals from other bays connected to the module A1A2_DC are described
below.
15.4.6.2 Signals in single breaker arrangement
M13542-6 v5
If the busbar is divided by bus-section disconnectors, the condition no other
disconnector connected to the bus-section must be made by a project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for both
bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,
corresponding signals from busbar B are used.
Section 1 Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_LINE
ABC_BC
ABC_LINE
(WA1)A1
(WA2)B1
(WA7)C C
B3
A3
en04000493.vsd
AB_TRAFO
AB_TRAFO
A2
B2
IEC04000493 V1 EN-US
Figure 339: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
1MRK 506 369-UEN B Section 15
Control
Line distance protection REL670 2.2 IEC 675
Application manual

Table of Contents

Related product manuals