If the denominator in equation 384 is called B and Z0m is simplified to X0m, then
the real and imaginary part of the reach reduction factor for the overreaching zones
can be written as:
( )
( )
( ) ( )
2 2
0 Re
Re 0 1
Re Im
X m B
K
B B
×
= -
+
EQUATION1427 V2 EN-US (Equation 385)
( )
( )
( ) ( )
2 2
0 Im
Im 0
Re Im
X m B
K
B B
×
=
+
EQUATION1428 V2 EN-US (Equation 386)
Parallel line is out of service and earthed in both ends
GUID-EC052207-C9AF-47EC-999A-BD485378FD9E v1
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit
for the single phase-to-earth faults.
Set the values of the corresponding zone (zero-sequence resistance and reactance)
equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
+
è ø
ç ÷
æ ö
×=
EQUATION561 V1 EN-US (Equation 387)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
–
è ø
ç ÷
æ ö
×=
EQUATION562 V1 EN-US (Equation 388)
8.13.4.7 Setting of reach in resistive direction
GUID-43EE13AF-BEBC-4A13-95B3-53C28B9164CB v3
Set the resistive reach R1 independently for each zone.
Set separately the expected fault resistance for phase-to-phase faults RFPP and for
the phase-to-earth faults RFPE for each zone. For each distance zone, set all
remaining reach setting parameters independently of each other.
The final reach in resistive direction for phase-to-earth fault loop measurement
automatically follows the values of the line-positive and zero-sequence resistance,
and at the end of the protected zone is equal to equation
389.
Section 8 1MRK 506 369-UEN B
Impedance protection
400 Line distance protection REL670 2.2 IEC
Application manual