R
jX
ArgLd
(ZMRPSB)
ArgLd
(FDPSPDIS)
jX
R
IEC09000225-2-en.vsdx
IEC09000225 V2 EN-US
Figure 225: Impedance diagrams with corresponding impedances under
consideration
The outer boundary of oscillation detection characteristic in forward direction
RLdOutFw should be set with certain safety margin K
L
compared to the minimum
expected load resistance R
Lmin
. When the exact value of the minimum load
resistance is not known, the following approximations may be considered for lines
with a rated voltage of 400 kV:
K
L
= 0.9 for lines longer than 150 km
K
L
= 0.85 for lines between 80 and 150 km
K
L
= 0.8 for lines shorter than 80 km
Section 8 1MRK 506 369-UEN B
Impedance protection
412 Line distance protection REL670 2.2 IEC
Application manual