EasyManua.ls Logo

ABB REL670 2.2 IEC - Page 505

ABB REL670 2.2 IEC
908 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Substation A
Substation B
Z
lineAB,1
(pos. seq)
Z
lineAB,0
(zero seq)
Z
lineBC,1
(pos. seq)
Z
lineBC,0
(zero seq)
U
0A
U
0B
3I
0
Phase to earth fault
R
N
Z
T,1
(pos. seq)
Z
T,0
(zero seq)
Source impedance
Z
sc
(pos. seq)
en06000654.vsd
IEC06000654 V1 EN-US
Figure 274: Equivalent of power system for calculation of setting
The residual fault current can be written:
phase
0
1 0 f
3U
3I
2 Z Z 3 R
=
× + + ×
EQUATION1948 V1 EN-US
(Equation 473)
Where
U
phase
is the phase voltage in the fault point before the fault
Z
1
is the total positive sequence impedance to the fault point. Z
1
= Z
sc
+Z
T,1
+Z
lineAB,1
+Z
lineBC,1
Z
0
is the total zero sequence impedance to the fault point. Z
0
= Z
T,0
+3R
N
+Z
lineAB,0
+Z
lineBC,0
R
f
is the fault resistance.
The residual voltages in stations A and B can be written:
( )
0A 0 T,0 N
U 3I Z 3R= × +
EQUATION1949 V1 EN-US
(Equation 474)
OB 0 T,0 N lineAB,0
U 3I (Z 3R Z )= × + +
EQUATION1950 V1 EN-US (Equation 475)
1MRK 506 369-UEN B Section 9
Current protection
Line distance protection REL670 2.2 IEC 499
Application manual

Table of Contents

Related product manuals