The connections are similar in all SESRSYN functions, apart from the breaker
position indications. The physical analog connections of voltages and the
connection to the IED and SESRSYN function blocks must be carefully checked in
PCM600. In all SESRSYN functions the connections and configurations must
abide by the following rules: Normally apparatus position is connected with
contacts showing both open (b-type) and closed positions (a-type).
WA1_QA1:
B1QOPEN/CLD = Position of TIE_QA1 breaker and belonging disconnectors
B2QOPEN/CLD = Position of WA2_QA1 breaker and belonging
disconnectors
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
UB1OK/FF = Supervision of WA1_MCB fuse
UB2OK/FF = Supervision of WA2_MCB fuse
ULN1OK/FF = Supervision of LINE1_MCB fuse
ULN2OK/FF = Supervision of LINE2_MCB fuse
Setting CBConfig = 1 1/2 bus CB
TIE_QA1:
B1QOPEN/CLD = Position of WA1_QA1 breaker and belonging
disconnectors
B2QOPEN/CLD = Position of WA2_QA1 breaker and belonging
disconnectors
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
UB1OK/FF = Supervision of WA1_MCB fuse
UB2OK/FF = Supervision of WA2_MCB fuse
ULN1OK/FF = Supervision of LINE1_MCB fuse
ULN2OK/FF = Supervision of LINE2_MCB fuse
Setting CBConfig = Tie CB
WA2_QA1:
B1QOPEN/CLD = Position of WA1_QA1 breaker and belonging
disconnectors
B2QOPEN/CLD = Position of TIE_QA1 breaker and belonging disconnectors
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
UB1OK/FF = Supervision of WA1_MCB fuse
UB2OK/FF = Supervision of WA2_MCB fuse
ULN1OK/FF = Supervision of LINE1_MCB fuse
ULN2OK/FF = Supervision of LINE2_MCB fuse
Setting CBConfig = 1 1/2 bus alt. CB
1MRK 506 369-UEN B Section 15
Control
Line distance protection REL670 2.2 IEC 607
Application manual