Using PTP for synchronizing the MU
SAM600 VT SAM600 CT
SAM600 TS
IED
PTP
9-2
IEC17000040-1-en.vsdx
IEC17000040 V1 EN-US
Figure 412: Setting example with PTP synchronization
Settings on the local HMI under Main menu/Configuration/Time/
Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:
• HwSyncSrc: is not used as the SW-time and HW-time are connected with each
other due to PTP
• SyncLostMode : set to Block to block protection functions if time
synchronization is lost or set to BlockOnLostUTC if the protection functions
are to be blocked when global common synchronization is lost
• SyncAccLevel: can be set to 1μs since this corresponds to a maximum phase
angle error of 0.018 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Communication/
Ethernet configuration/Access point/AP_X:
• Operation: On
• PTP: On
1MRK 506 369-UEN B Section 21
Station communication
Line distance protection REL670 2.2 IEC 823
Application manual