communication network (IEC 61850-8-1). The SyncMaster can have the following
values:
Off
SNTP -Server
Set the course time synchronizing source (CoarseSyncSrc) to Off
when GPS time synchronization of line differential function is used.
Set the fine time synchronization source (FineSyncSource) to GPS.
The GPS will thus provide the complete time synchronization. GPS
alone shall synchronize the analogue values in such systems.
IEEE 1588 (PTP)
GUID-424227EC-74A1-4628-8948-C1876840ABFE v3
Precision Time Protocol (PTP) is enabled/disabled using the Ethernet configuration
tool /ECT) in PCM600.
PTP can be set to On,Off or Slave only. When set to Slave only the IED is
connected to the PTP-group and will synchronize to the grandmaster but cannot
function as the grandmaster.
A PTP-group is set up by connecting the IEDs to a network and enabling PTP. To
set one IED as the grandmaster change Priority2 to 127 instead of the default 128.
IEC16000089-1-en.vsdx
IEC16000089 V1 EN-US
Figure 429: Enabling PTP in ECT
The PTP VLAN tag must have the same value in station clock and in the IED. The
default value is set to 0.
The PTP VLAN tag does not need to be the same on all access points in one IED. It
is possible to mix as long as they are the same for all devices on each subnet.
1MRK 506 369-UEN B Section 24
Basic IED functions
Line distance protection REL670 2.2 IEC 873
Application manual