EasyManua.ls Logo

ABB REL670 2.2 IEC - Page 889

ABB REL670 2.2 IEC
908 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
kzone1 sr
R
al alreq ct L
2
pr
r
I I
S
E E k R R
I
I
×
æ ö
³ = × × + +
ç ÷
è ø
EQUATION1081 V2 EN-US (Equation 540)
where:
I
kmax
Maximum primary fundamental frequency current for close-in forward and
reverse faults (A)
I
kzone1
Maximum primary fundamental frequency current for faults at the end of zone 1
reach (A)
I
pr
The rated primary CT current (A)
I
sr
The rated secondary CT current (A)
I
r
The rated current of the protection IED (A)
R
ct
The secondary resistance of the CT (W)
R
L
The resistance of the secondary wire and additional load (W). In solidly earthed
systems the loop resistance containing the phase and neutral wires should be
used for phase-to-earth faults and the resistance of the phase wire should be
used for three-phase faults.
In isolated or high impedance earthed systems the resistance of the single
secondary wire can always be used.
S
R
The burden of an IED current input channel (VA). S
R
=0.020 VA/channel for I
r
=1
A and S
R
=0.150 VA/channel for I
r
=5 A
a This factor depends on the design of the protection function and can be a
function of the primary DC time constant of the close-in fault current.
k This factor depends on the design of the protection function and can be a
function of the primary DC time constant of the fault current for a fault at the set
reach of zone 1.
The a- and k-factors have the following values for the different types of distance
function:
High speed distance: (ZMFPDIS and ZMFCPDIS)
Quadrilateral characteristic:
a = 1 for primary time constant Tp £ 400 ms
k = 3 for primary time constant Tp £ 200 ms
Mho characteristic:
a = 2 for primary time constant Tp £ 400 ms (For a = 1 the delay in operation
due to saturation is still under 1.5 cycles)
k = 3 for primary time constant Tp £ 200 ms
Quadrilateral distance: (ZMQPDIS, ZMQAPDIS and ZMCPDIS, ZMCAPDIS and
ZMMPDIS, ZMMAPDIS)
a = 1 for primary time constant Tp £ 100 ms
a = 3 for primary time constant Tp > 100 and £ 400 ms
k = 4 for primary time constant Tp £ 50 ms
k = 5 for primary time constant Tp > 50 and £ 150 ms
Mho distance: (ZMHPDIS)
a = 1 for primary time constant Tp £ 100 ms
a = 3 for primary time constant Tp > 100 and £ 400 ms
k = 4 for primary time constant Tp £ 40 ms
k = 5 for primary time constant Tp > 40 and £ 150 ms
1MRK 506 369-UEN B Section 25
Requirements
Line distance protection REL670 2.2 IEC 883
Application manual

Table of Contents

Related product manuals