EFPADM1
O:51|T:5|I:1
BLOCK
RELEASE
TRIP
PICKUP
EFPADM2
O:18|T:5|I:2
BLOCK
RELEASE
TRIP
PICKUP
EFPADM3
O:19|T:5|I:3
BLOCK
RELEASE
TRIP
PICKUP
OR6
O:123|T:2.5|I:56
B1
B2
B3
B4
B5
B6
O
EFPADM2_21YN-2_TRIP
EFPADM2_21YN-2_TRIP
EFPADM3_21YN-3_TRIP
EFPADM3_21YN-3_TRIP
EFPADM1_21YN-1_TRIP
EFPADM1_21YN-1_TRIP
EFPADM1_21YN-1_PICKUP
EFPADM2_21YN-2_PICKUP
EFPADM3_21YN-3_PICKUP
EFPADM_TRIP
GUID-774F99EE-223C-4A4E-9B2B-EED1A1CCA381 V1 EN
Figure 118: Admittance-based ground-fault protection function
Phase discontinuity protection PDNSPTOC1_46PD protects for interruptions in the
normal three-phase load supply, for example, in downed conductor situations. The
function is blocked in case of detection of a failure in secondary circuit of voltage
transformer.
PDNSPTOC1
O:36|T:5|I:1
BLOCK TRIP
PICKUP
PDNSPTOC1_46PD_TRIP
PDNSPTOC1_46PD_PICKUP
CCSPVC1_CCM_FAIL
GUID-42E0E6F1-17A3-4B6C-9A82-DF6A224E0120 V1 EN
Figure 119: Phase discontinuity protection
Three-phase thermal protection for feeders, cables and distribution transformers
T1PTTR1_49F-1 detects overloads under varying load conditions. The BLK_CLOSE
output of the function is used to block the closing operation of circuit breaker.
T1PTTR1
O:37|T:5|I:1
BLOCK
ENA_MULT
AMB_TEMP
TRIP
PICKUP
ALARM
BLK_CLOSE
T1PTTR1_49F_BLK_CLOSE
T1PTTR1_49F_TRIP
T1PTTR1_49F_PICKUP
T1PTTR1_49F_ALARM
GUID-2EF3F93A-0087-4039-BFAA-B3678F99687B V1 EN
Figure 120: Thermal overcurrent protection function
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 111
Application Manual