ABB Relion 615 series - Default Disturbance Recorder Settings

ABB Relion 615 series
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 24: Default connections for LEDs
LED Default usage ID Label description
1 Circuit breaker close enabled LED_CBcloseenabled_1 CB close enabled
2 Overcurrent protection trip LED_Overcurrent_1 Overcurrent
3 Ground-fault protection trip LED_EarthFault_1 Ground-fault
4 Current unbalance protection
trip
LED_PhaseUnbalance_1 Phase unbalance
5 Sequence voltage protection
trip
LED_NPSOrPPSvoltage_1 Sequence voltage
6 Overvoltage or residual
overvoltage protection trip
LED_OVorResidualVoltage_1 OV / Residual voltage
7 Thermal overload alarm LED_ThermalOverload_1 Thermal overload
8 Undervoltage or frequency
protection trip
LED_UVorFrequency_1 UV / Frequency
9 Supervision alarm LED_Supervision_1 Supervision
10 Circuit breaker condition
monitoring alarm
LED_CBConditionMonitoring_
1
CB condition monitoring
11 - - -
3.5.2.2 Default disturbance recorder settings
Table 25: Default disturbance recorder analog channels
Channel
Description
1 IL1
2 IL2
3 IL3
4 Io
5 U1
6 U2
7 U3
8 -
9 -
10 -
11 -
12 -
Section 3 1MAC109016-MB C
REF615 standard configurations
102 REF615 ANSI
Application Manual