Binary output Description Connector pins
X100-PO3 Open circuit breaker/trip coil 1 X100:15-19
X100-PO4 Open circuit breaker/trip coil 2 X100:20-24
X110-SO1 Upstream overcurrent blocking X110:14-16
X110-SO2 Overcurrent trip alarm X110:17-19
X110-SO3 Ground-fault trip alarm X110:20-22
X110-SO4 - X110:23-24
X110-HSO1 Arc protection instance 1 trip activated X110:15-16
X110-HSO1 Arc protection instance 2 trip activated X110:19-20
X110-HSO1 Arc protection instance 3 trip activated X110:23-24
X130-SO1 - X130:10-12
X130-SO2 - X130:13-15
X130-SO3 - X130:16-18
Table 12: Default connections for LEDs
LED Default usage ID Label description
1 Non-directional overcurrent trip LED_Overcurrent_1 Overcurrent
2 Non-directional ground-fault
trip
LED_EarthFault_1 Ground-fault
3 Sensitive ground-fault trip LED_SensitiveEarthFault_1 Sensitive ground-fault
4 Negative sequence overcurrent
or phase discontinuity trip
LED_PhaseUnbalance_1 Phase unbalance
5 Thermal overload alarm LED_ThermalOverload_1 Thermal overload
6 Breaker failure trip LED_BreakerFailure_1 Breaker failure
7 Disturbance recorder triggered LED_DisturbRecTriggered_1 Disturb. rec. triggered
8 Circuit breaker condition
monitoring alarm
LED_CBConditionMonitoring_
1
CB condition monitoring
9 Trip circuit supervision alarm LED_TripCircuitFailure_1 Trip circuit failure
10 Arc flash detection LED_ArcDetected_1 Arc detected
11 Autoreclose in progress LED_AutorecloseInProgress_1 Autoreclose shot in progr.
3.3.2.2 Default disturbance recorder settings
Table 13: Default disturbance recorder analog channels
Channel
Description
1 IL1
2 IL2
3 IL3
Table continues on next page
Section 3 1MAC109016-MB C
REF615 standard configurations
44 REF615 ANSI
Application Manual