TCSSCBR1
O:74|T:5|I:1
BLOCK ALARM
TCSSCBR2
O:75|T:5|I:2
BLOCK ALARM
OR
O:76|T:2.5|I:13
B1
B2
O
TCSSCBR1_TCM-1_ALARM
TCSSCBR1_TCM-1_ALARM
TCSSCBR2_TCM-1_ALARM
TCSSCBR2_TCM-1_ALARM
TCSSCBR_BLOC KING
TCSSCBR_BLOC KING
TCSSCBR_ALARM
GUID-09D826A2-9C1F-45E2-8382-FFC58B98DAE7 V1 EN
Figure 32: Trip circuit supervision function
OR6
O:73|T:2.5|I:19
B1
B2
B3
B4
B5
B6
O
TRPPTRC2_86/94-2_TRIP
X120_BI3_CB_OPEN
TRPPTRC1_86/94-1_TRIP TCSSCBR_BLOCKING
GUID-A0E5F33A-B395-4EE7-92A9-C1222EF942BD V1 EN
Figure 33: Logic for blocking of trip circuit supervision
3.3.3.4 Functional diagrams for control and interlocking
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input
can be activated using the configuration logic, which is based on the status of the trip
logics. However, other signals can be connected based on the application needs.
The SYNC_ITL_BYP input can be used, for example, to always enable the closing of the
circuit breaker when the circuit breaker truck is in the test position. SYNC_ITL_BYP
overrides, for example, active interlocking conditions when the circuit breaker truck is
closed in service position.
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 59
Application Manual