EasyManua.ls Logo

ABB Relion 615 series - Default I;O Connections

ABB Relion 615 series
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.4.2.1 Default I/O connections
Table 15: Default connections for analog inputs
Analog input
Description Connector pins
IA Phase A current X120:7-8
IB Phase B current X120:9-10
IC Phase C current X120:11-12
IG Residual current IG X120:13-14
VA Phase voltage VA X130:11-12
VB Phase voltage VB X130:13-14
VC Phase voltage VC X130:15-16
VG Residual voltage VG X130:17-18
Table 16: Default connections for binary inputs
Binary input Description Connector pins
BIO0005 BIO0007
X110-BI1 MCB open X110:1-2 X110:1,5
X110-BI2 Directional ground-fault protection's basic angle control X110:3-4 X110:2,5
X110-BI3 - X110:5-6 X110:3,5
X110-BI4 - X110:7-6 X110:4-5
X110-BI5 - X110:8-9 X110:6,10
X110-BI6 - X110:10-9 X110:7,10
X110-BI7 - X110:11-12 X110:8,10
X110-BI8 - X110:13-12 X110:9-10
X120-BI1 Blocking of overcurrent instantaneous stage X120:1-2
X120-BI2 Circuit breaker closed position indication X120:3-2
X120-BI3 Circuit breaker open position indication X120:4-2
X120-BI4 Lock-out reset X120:5-6
X130-BI1 - X130:1-2
X130-BI2 - X130:3-4
X130-BI3 - X130:5-6
X130-BI4 - X130:7-8
Section 3 1MAC109016-MB C
REF615 standard configurations
68 REF615 ANSI
Application Manual

Table of Contents

Other manuals for ABB Relion 615 series

Related product manuals