GUID-3ECF87A5-74E7-424E-B334-6B2F10386317 V1 EN
Figure 130: General pickup and trip signals
The trip signals from the protection functions are connected to the two trip logics
TRPPTRC1_86/94-1 and TRPPTRC2_86/94-2. The output of these trip logic functions
are available at binary outputs X100:PO3 and X100:PO4. Both the trip logic functions are
provided with lockout and latching function, event generation and the trip signal duration
setting. If the lockout operation mode is selected, binary input has been assigned to
RST_LKOUT input of both the trip logic to enable external reset with a push button.
Three other trip logics TRPPTRC3...5_86/94-3…5 are also available if the relay is
ordered with high speed binary outputs options.