GUID-9CDF8457-46A0-40CA-9D2A-A1548D4800D8 V1 EN
Figure 138: Logic for circuit breaker monitoring alarm
Two separate trip circuit supervision functions are included: TCSSCBR1_TCM-1 for
power output X100:PO3 and TCSSCBR2_TCM-2 for power output X100:PO4. Both the
functions are blocked by the master trips TRPPTRC1_86/94-1 and TRPPTRC2_86/94-2
and the circuit breaker open signal.
It is assumed that there is no external resistor in the circuit breaker tripping
coil circuit connected in parallel with the circuit breaker normally open
auxiliary contact.
TCSSCBR1
O:110|T:5|I:1
BLOCK ALARM
TCSSCBR2
O:111|T:5|I:2
BLOCK ALARM
OR
O:112|T:2.5|I:16
B1
B2
O
TCSSCBR_BLOC KING
TCSSCBR_BLOC KING
TCSSCBR1_TCM-1_ALARM
TCSSCBR1_TCM-1_ALARM
TCSSCBR2_TCM-2_ALARM
TCSSCBR2_TCM-2_ALARM
TCSSCBR_ALARM
GUID-DDFABA18-F276-40E5-84C3-1AAA5442C3B6 V1 EN
Figure 139: Trip circuit supervision function
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 123