CBXCBR1
O:79|T:5|I:1
POSOP EN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLO SE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
TRUE
CBXCBR1_52-1_ENA_CLOSE
CBXCBR1_52-1_EXE_CL
X110_BI3_CB_OPEN
X110_BI4_CB_CLOSED
CBXCBR1_52-1_BLK_CLOSE
CBXCBR1_52-1_EXE_OP
FALSE
CBXCBR1_52-1_AU_OPEN
CBXCBR1_52-1_AU_CLOSE
CBXCBR1_52-1_CLOSE_ENAD
CBXCBR1_52-1_SELECTED
GUID-40DD515C-E66E-472B-BCA6-5BAA4146EA4B V1 EN
Figure 142: Circuit breaker control logic: Circuit breaker 1
OR
O:86|T:2.5|I:10
B1
B2
O
CB_CLOSE_COMMANDCBXCBR1_52-1_EXE_CL
DARREC1_79_CLOSE_CB
GUID-9B4C6575-7430-4D76-BF0A-AC790D93DFCD V1 EN
Figure 143: Circuit breaker control logic: Signals for the closing coil of circuit breaker
1
OR6
O:85|T:2.5|I:22
B1
B2
B3
B4
B5
B6
O
CB_OPEN_COMMANDCBXCBR1_52-1_EXE_OP
TRPPTRC1_86/94-1_TRIP
DARREC1_79_OPEN_CB
GUID-8083F101-48DA-4C7F-9F26-0A0A98A19A85 V1 EN
Figure 144: Circuit breaker control logic: Signals for the opening coil of circuit breaker
1
NOT
O:72|T:2.5|I:3
IN OUT
AND6
O:78|T:2.5|I:0
B1
B2
B3
B4
B5
B6
O
NOT
O:73|T:2.5|I:2
IN OUT
TRPPTRC2_86/94-2_TRIP
CBXCBR1_52-1_ENA_CLOSETRPPTRC1_86/94-1_TRIP
GUID-1560EADA-0523-412F-A05C-55A6C9842A49 V1 EN
Figure 145: Circuit breaker close enable logic
Connect the higher-priority conditions before enabling the closing of
circuit breaker. These conditions cannot be bypassed with bypass feature
of the function.
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 125
Application Manual