EFHPTOC1
O:103|T:5|I:1
BLOCK
ENA_MULT
TRIP
PICKUP
EFLPTOC1
O:26|T:5|I:1
BLOCK
ENA_MULT
TRIP
PICKUP
EFIPTOC1
O:32|T:2.5|I:1
BLOCK
ENA_MULT
TRIP
PICKUP
EFHPTOC2
O:31|T:5|I:2
BLOCK
ENA_MULT
TRIP
PICKUP
CLD_62_1_TRIP
EFIPTOC1_50G-3_PICKUP
EFHPTOC2_50G-2_PICKUP
EFLPTOC1_51G_TRIP
EFHPTOC1_50G-1_TRIP
EFIPTOC1_50G-3_TRIP
EFHPTOC2_50G-2_TRIP
GUID-BFBB8FFE-06EE-4DA9-B151-9122E00D3E75 V1 EN
Figure 228: Non-directional ground-fault protection
Two stages are offered for directional ground-fault protection. By default the stages
DEFHPDEF1_67/50N-1 and DEFHPDEF2_67/50N-2 are blocked by the fuse failure
detection and the polarization choice is set to negative sequence voltage. Also by default,
these two functions are also not blocked by a cold load situation.
The polarization should never be set to “measured” as there is no
dedicated Vg input for this configuration. Setting polarization to Vg will
result in a settings error.
DEFHPDEF1
O:19|T:5|I:1
BLOCK
ENA_MULT
RCA_CTL
TRIP
PICKUP
DEFHPDEF2
O:18|T:5|I:2
BLOCK
ENA_MULT
RCA_CTL
TRIP
PICKUP
DEFHPDEF2_67_50N-2_PICKUP
DEFHPDEF1_67_50N-1_PICKUP
DEFHPDEF1_67_50N-1_TRIP
DEFHPDEF2_67_50N-2_TRIP
CCRDIF1_CCM_FAIL
CCRDIF1_CCM_FAIL
GUID-FFEAD23C-22CD-4ECD-8666-85AFD1F69D2D V1 EN
Figure 229: Directional calculated neutral overcurrent protections
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 175
Application Manual